ACTIVE HARMONIC FILTER

TECHNICAL DATA SHEET-TEC

Operating Temperature

+ 0° C to + 40° C in continuous operation, < 25° C recommended

Relative Humidity

0% to 95%

Operating Altitude

< 1000 m

Line Voltage

400 Volts, - 20% upto  + 15%

Phase / Wires

3 Phase networks with or without neutral conductor.

Frequency

50 + 8%

Compensating Current in Amps 20 A 30 A 45 A 60 A 90 A 120A
Compensating Neutral Current in Neutral 60A 90A 135A 180A 270A 360A
Operational Power 1000 W 1300 W 12000 W 2600 W 4200 W 5200 W
Sound Levels as per ISO 3476 <55dBA <55dBA <60dBA <60dBA <65dBA <65dBA
Dimension ( B x H x D ) in mm 540 x 680 x 280 540 x 680 x 280 540 x 780 x 325 540 x 780 x 325 2 x 540 x 680 x 280 2 x 540 x 680 x 280
Weights (in Kg) 65 65 110 110 2 x 110 2 x 110
Compensated Harmonic 2nd up to 25th Harmonics or specifically selectable
Compensation Factor THDI Consumer / THDI Network > 10 in nominal – compensation current.
Response Time > 40 ms
Overload disconnection Nominal Current limiting, current limiting duration
Inrush Current < 2 x nominal current (peak value)
Protection IPS 30 in accordance with IEC 529
Standards
Construction and Security: EN 50091-1
Philosophy: IEC 146
Protection: IPS 30 in accordance with IEC 529
Electromagnetic Compatibility
Fiel and Direction Bandage: EN 55011, Level A
Disturbance Stability – Electricity Discharges: IEC 1000-4-2, Level 3 & IEC 1000-4-3, Level3.
Disturbance Stability – Push Tensions: IEC 1000-4-4, and IEC 1000-4-5, Level 4

top