DYNAMIC POWER FACTOR CORRECTION SYSTEM

TECHNICAL DATA SHEET

Rated Voltage

440 Volts + 10% (nominal variation)

Rated Frequency

50 Hz + 2% (nominal variation)

Over Voltage

105% continuous
110% for 8 hours daily
120% for 5 minutes
130% for 1 minute

Overload

200% the rated current continuously

Configuration

Delta

Basic insulation level

3.0 kV rms (1 minute)

Capacitance rating tolerance

+ 5%

Pick up Current of Relay

20 mA

Relay Sensitivity

10 mA

Controller Switching Logic

Universal without any time delay

P.F Measurement

Micro Processor based four quadrant APFC Relay

Voltage for Auxiliary Circuits

230 V, 50 Hz

Relay Current Input Signal

By C.T on line …/5A or …/1A

Relay Voltage input

230 / 400 Volts

Service

Continuous

Installation

Indoor

Inpanel Temperature Class

0° C to + 60° C

Altitude

Upto 1000 meters above msl

Type of Capacitors

Dry, Self-Healing, Heavy Duty, Cylindrical, Metallised polypropylene capacitors with overpressure disconnector and external discharge resistors.

Dielectric Loss of Capacitors

< 0.2 Watts per KVAR & < 0.5 Watts per KVAR with discharge resistors.

Inrush current withstand capability of capacitors

> 300 times the rated current.

Metering

Digital Voltmeter & Ammeter
Optionally – Power Meter.

Panel Protection

Protection against:

Over-Load.
Short Circuit.
Earth Fault.

Alarm Signals

Low Voltage, Over Voltage, Low Current, High Current, Undercompensation, Insufficient capacitor power, Supply of Real Power, Harmonic Threshold, )vertemperature

Capacitor Step Switching Assembly

1600 Volts PIV Thyristors.

Point on Wave Switching.
Opto coupled Trigger Circuit.
Temperature rise alarm / trip options.

Protection Devices

MCCB ensures adequate overload & short circuit protection, current limiting feature and single phasing prevention.

Scope of Supply

Thyristor Switched capacitor panel complete with Busbars, LT power factor correction capacitors, MCCB, Thyristors, Trigger & contol circuitry , CTs, PTs for internal control completely wired inside powder coated panels.

Supervision of Erection & Commissioning.

Operating Conditions

The DPFC system is designed for safe and reliable operation in electrical installations with VTHD< 5% and ITHD< 8%.

























Top

Type Free Standing – Cubicle DPFC System
Model 1DV2 1DV2 1DV2 2DV2 2DV2 2DV2 2DV2 3DV2 3DV2 3DV2
Capacitors configuration (in KVAR) 5 + 10 + 20 10 + 20 + 20 10 + 10 + 20 + 20 10 + 10 + 20 + 40 10 + 10 + 20 + 20 + 40 10 + 10 + 20 + 20 + 60 10 + 10 + 20 + 20 + 80 10 +10 + 20 + 20 + 40 + 80 40 + 80 + 80 40 + 80 + 120
Dimension (excluding Baseframe / Stand )
Length-in mm 600 600 600 1100 1100 1100 1100 1200 1200 1200
Height-in mm 1275 1275 1275 1375 1375 1375 1375 2075 2075 2075
Depth-in mm 450 450 450 450 450 450 450 450 450 450

Type Free Standing – Cubicle DPFC System
Model 4DV2 4DV2 4DV2 4DV2 4DV2 4DV2 4DV2
Capacitors configuration (in KVAR) 20 + 40 + 80 + 80 + 80 20 + 40 + 80 + 80 + 120 20 + 40 + 80 + 120 + 120 20 + 40 + 40 + 80 + 120 + 120 20 + 40 + 80 + 80 + 120 + 120 20 + 40 + 80 + 120 + 120 + 120 40 + 80
+ 120 + 120
+ 120 + 120
Dimension (excluding Baseframe / Stand )
Length-in mm 1800 1800 1800 1800 1800 1800 1800
Height-in mm 2075 2075 2075 2075 2075 2075 2075
Depth-in mm 450 450 450 450 450 450 450