PASSIVE / ANTI RESONANT HARMONIC FILTER SYSTEM

TECHNICAL DATA SHEET

Rated Voltage

415 Volts AC + 10%

Rated Frequency

50 Hz + 3%

Type of System

De-Tuned System : Frequency ranging from 136 Hz to 189 Hz, …….

Tuned System : Frequency ranging from 210 Hz to 250 Hz, ……….

Over Voltage

105% continuous ;

110% for 8 hours daily;
120% for 5 minutes;
130% for 1 minute

Overload

200% the rated current continuously

Configuration

Delta

Basic insulation level

3.0 kV rms (1 minute)

Capacitance rating tolerance

+ 5%

Steps of Controller

6 Steps (or) 12 Steps

Pick up Current of Relay

20 mA

Relay Sensitivity

10 mA

Controller Switching Logic

First In First Out, with a reconnection time delay of
1 minute.

Control Modes

Automatic, Semi-Automatic, Emergency/Manual

P.F Measurement

Micro Processor based four quadrant APFC Relay

P.F Display

Through LED updated dynamically

Voltage for Auxiliary circuits

230 V, 50 Hz

Relay Current Input Signal

ByC.T on line …/5A or …/1A

Relay Voltage input

230 / 400 Volts

Service

Continuous

Installation

Indoor

Inpanel Temperature Class

0° C to + 60° C

Altitude

Upto 1000 meters above msl

Type of Capacitors

Dry, Self-Healing, Heavy Duty, Cylindrical, Metallised polypropylene capacitors with overpressure disconnector and external discharge resistors.

Dielectric Loss of Capacitors

< 0.2 Watts per KVAR & < 0.5 Watts per KVAR with discharge resistors.

Inrush current withstand capability of capacitors

> 300 times the rated current.

Metering

Digital Voltmeter & AmmeterOptionally – Power Meter.

Panel Protection

 

Protection against :   

Over-Load.
Short Circuit. 
Earth Fault.

Alarm Signals

Under compensation, Faults in voltage & current circuits, High harmonic levels, Fault in capacitor stages & Defective capacitor stages.

Capacitor Step Switching Assembly

Capacitor Duty Contactors with pre insertion resistors and low contact bounce. 

Harmonic Filter Reactors

Insulation Class – “F”

Core Linearity – 1.75 times the rated current.
Ref. Design Ambient Temperature – 60° C
Self Cooling Thermistor monitored.

Protection Devices

MCB / MCCB ensuring adequate overload & short circuit protection, current limiting feature and single phasing prevention.

Scope of Supply

Contactor switched capacitor panel complete with Busbars, LT power factor correction capacitors, MCCB, Contactor, CTs, PTs for internal control completely wired inside powder coated panel
Supervision of Commissioning.

Operating Conditions

The APFC system is designed for safe and reliable operation in electrical installations with VTHD< 10%.


Type

Free Standing – Cubicle Passive De-Tuned Filter System

Model

1FV1

1FV1

2FV1

2FV1

2FV1

3FV1

3FV1

4FV1

4FV1

5FV1

5FV1

5FV1

5FV1

5 FV1

Capacitors configuration (KVAR@525 V)

20 x 4

20 x 2 +
40 x 2

40 x 4

40 x 3
+
80 x 1

40 x 2
+
80 x 2

40 x 4
+
80 x 2

40 x 2
+
80 x 4

40 x 4
+
80 x 4

40 x 2
+
80 x 6

40 x 4
+
80 x 6

40 x 2
+
80 x 8

40 x 4
+
80 x 8

40 x 2
+
80 x 10

80 x 12

Dimension (excluding Baseframe / Stand )

Length- mm

600

600

1000

1000

1000

1200

1200

1500

1500

1800

1800

1800

1800

1800

Height- mm

1800

1800

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

Depth- mm

400

400

550

550

550

550

550

550

550

550

550

550

550

550


Type

Free Standing – Cubicle Passive Tuned Filter System

Model

1FV1

1FV1

2FV1

2FV1

2FV1

3FV1

3FV1

4FV1

4FV1

5FV1

5FV1

5FV1

5FV1

5 FV1

Capacitors configuration (KVAR@525 V)

40 x 2

40 x 3

80 x 2

40 x 1
+
80 x 2

80 x 3

80 x 4

80 x 5

80 x 6

80 x 7

80 x 8

80 x 9

80 x 10

80 x 11

80 x 12

Dimension (excluding Baseframe / Stand )

Length- mm

600

600

1000

1000

1100

1100

1200

1200

1500

1500

1800

1800

1800

1800

Height- mm

1800

1800

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

2100

Depth- mm

400

400

550

550

550

550

550

550

550

550

550

550

550

550

























Top