| Mechanical Construction |
Cylindrical Aluminium Case with M12 Mounting Stud at bottom. Top cover has Terminals and Discharge Resistors. Diaphragm Cover arrangement provides Over Pressure Disconnection facility. |
 |
| Design |
Self Healing, Dry Type, Heavy Duty, filled with Flame inhibiting Mineral Filler |
| Termination |
Patented Tension Spring arrangement with adequate clearances. |
| Power Loss |
0.5 Watts / KVAR measured at connecting terminals including discharge resistor and 0.2 Watts / KVAR at capacitor coils. |
| Temperature Class |
- 40° C + 60° C
Case Temperature TC upto 75° C |
| Current Overload capacity |
2 Times the rated rms current continuously. Inrush peaks upto 350 Times rated current. |
| Voltage Overload capacity |
10% - 12 hours daily, 15% for 30 minutes daily, 20% for 5 minutes daily & 30% for 1 minute daily. |
| Safety Features |
Self Healing, Dry Type, Over Pressure Disconnector, Integral External Discharge Device, Tension Spring Terminals. |
OVER LOAD PRESSURE DISCONNECTOR |
| Standards |
BIS : 13340–1993 & BIS : 13341–1992, IEC:831 Part 1&2, EN 60831, VDE 0560 Part 41 |