JANITZA - POWER FACTOR CONTROLLER PROPHI

SALIENT FEATURES
Indication of U, I, f, Q, P, S, cos-phi, all odd harmonics etc.
Indication of the capacitor currents measured indirectly and of the switching operations of each capacitor stage.
Zero voltage releasing within 15 ms
Controlling of external semiconductor switches (max. 50 switchings per second)
Automatic or manual configuration
Capacitor power programmable for each stage
Alarm output
Temperature sensor for ventilator control
RS485 interface , Modbus RTU / Profibus DP (V0)

APPLICATION:

Reactive power compensation plants are used to decrease the load of cables and power distributions caused by inductive currents and to save reactive power costs. The power factor controller is a main part of such a plant and connects or disconnects capacitor stages automatically. The power factor controller Prophi is suitable for the use in conventional or dynamic reactive power compensation systems, and a mixed
operation is possible as well.


General operation

The one phase electronic measuring system detects the reactive and real vectors of current through current and voltage path. By means of these values the controller computes the phase divergence between the fundamentals of current and voltage, and compares it to the set phase divergence. In case of a difference, capacitor contactors will be switched on or off. Here the reactive power controller distinguishes the switching of capacitors via contactors or semiconductor switches. The controlling via capacitor contactors is carried out optimized, which means, that the target cos-phi is reached by as less switching operations as possible. Transistor outputs for the controlling of semiconductor switches compensate any difference.


Overtemperature disconnection

With the overtemperature disconnection, connected stages can be disconnected to lower the inner temperature and to protect the capacitors. An upper and lower limit can be set with a switch off time.


Ventilator control

One relay output can be used for ventilator control, where an upper and lower limit is programmable


Properties
Indication of U, I, f, Q, P, S, cos-phi, all odd harmonics from 1-19 of current and voltage
Indication of the capacitor currents measured indirectly
Indication of the switching operations of each capacitor stage
Indication of the total switch-on-time of each capacitor stage
Zero voltage releasing within 15 ms
Choke degree in % for each stage programmable from 0-20%
Setting of the discharge time for all contactor stages of 0-1200 seconds.
Capacitor power programmable for each stage
Temperature feeler for ventilator control
Overtemperature disconnection programmable
Controlling of external semiconductor switches (max. 50 switchings per second)
Current transformer input for ../1A and ../5A
Automatic or manual configuration
Password protection
External switchable target cos phi
Alarm output programmable for
  Under voltage recognition
  Over voltage recognition
  Under compensation
  Current interruption
  Measuring current exceeding
  Harmonic threshold
  Supply of real power
  Overtemperature