| TECHNICAL DATA SHEET – EMR 1100 S / EMR 1100 |
| Mode of Connection |
Phase to Phase connection (OR) Phase to Neutral Connection.
Current via Current Transformer in optional phase. |
| Operating Voltage |
Supply Voltage : 230 Volts ~ / 400 Volts ~. Mains Terminal Voltage : 220 V ~ to 240 V ~ / 380 V ~ to 420 V ~
Absolute permissible / threshold values :198 V~ to 264 V~ / 342 V~ to 462 V~
Note: The terminals for 230 V and 400 V are internally bridged. |
| Voltage Path |
Voltage input 100 V ~ … 660 V ` |
| Frequency |
50 Hz / 60 Hz ( 48 to 62 Hz) |
| Consumption |
Approximately 9-13 VA at 0 to 12 Switched-on control contacts. |
| Current Path |
For Current Transformer …/1A ~ to …/5A ~ |
| Consumption in Current Path |
Max. 1.8 VA at 5 A~ rated current of the CT |
| Control Contacts |
12 potential – free relay contacts |
| Loading capacity of the Control contacts |
Switching Voltage :
380 VAC (according to VDE 0110 part B); 250 VAC(according to VDE 0110 part C)
Switching current upto 2 x 5 A max., Switching load upto 1800 VA max. |
| Fault Signal contacts |
Loading capacity 250 V ~, 3 A |
| No-Voltage Trip |
Voltage loss of longer than 15 ms |
| Zero Current Trip |
Current loss of longer than 3 secs. |
Operating Elements
|
Foil Keyboard with 4 buttons |
| LED Indicators |
18 LEDs, 4 ½ character digital display |
| Temperature Range |
- 20 Deg. C to + 60 Deg. C |
| Enclosure material |
Black Synthetic Plastic, Flame resistant to UL-94, Class V0 |
| Fastening |
Through the front panel by means of a screwdriver. |
| Front Panel Dimension |
144 mm x 144 mm ( to DIN 43 700 ) |
| Panel Cut Out |
138 mm x 138 mm ( to DIN 43 700 ) |
| Mounting Depth |
105 mm |
| Weight |
ca. 1.2 Kgs. |
| Terminals |
Plug-in connector blocks (supplied with the control relay) |
| Enclosure Protection |
Terminals – IP 20 ; Casing – IP 54 (when using sealing ring) |
| Design |
EN 50 081 – 1, EN 50 082 – 2, EN 61 010 & (VDE 0411 part 1) Protection Class II, (if insulated fixing screws are used) |
| Fusing |
External, max. 4A |