Protection Class |
II = without protective wire |
Humidity |
15% up to 95% without dew |
Resistance against interference (Industrial Area) |
EN50082-2:1995; IEC1000-4-3, 10V/m
|
| IEC1000-4-4, 2kV; IEC1000-4-2, 8kV |
Interference radiation (residential areas) |
EN55011 10.1997 |
Safety Guidelines |
EN61010-1 03.1994 + A2 05.1996; IEC1010-1 |
Measuring voltage |
L – N : 196 .. 275 V AC ; L – L : 340 – 475 V AC
(other range also available) |
Current Measurement |
Max. 300 VAC against earth |
Rated Current at ../5A (../1A) |
5A (1A) |
Voltage measurement |
Max. 300VAC against earth. |
Fuse |
2 A .. 6 A (medium time lag type) |
Switching Frequency |
Max. 10 Hz. (50ms pulse width) |
Operating Current |
Max. 50 mA. (not short-circuit-proof) |
One wire, multiple-wire, fine wire |
0.08 – 2.5 mm2 |
Pin contacts |
1.5 mm2, only one wire may be connected at one clamp. |