SCHEME Load Centric Filter System:
Group Control Filter System:
IMPACT OF HARMONICS ON CAPTIVE POWER PLANT LOADING POLYESTER FILM PLANT PREAMBLE The plant has Polyester Film Production process. To have reliable and continuous production process, the Power Supply is by Captive Genset. Problem was reported on the captive genset performance, which could not be loaded to its maximum level and was experiencing rotor jerking & rotor retardation causing over temperature tripping.
An extensive Power Quality Analysis was done at site and the following are the observations.
All these individual components increase the heat in the winding, thereby increasing the Temperature.
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Feeder Reference |
System |
Extruder Motor |
BARON-ASHF/200 |
DC Drive |
BARON-ASHF/100 |
Film Plant – 1 |
BARON-ASHF/100 |
Film Plant – 2 |
BARON-ASHF/150 |
PERFORMANCE WITH BARON-ASHF SYSTEMS
Parameters |
Without BARON-ASHF System |
With BARON-ASHF System |
Electrical Parameters |
||
Voltage Harmonics at 11 KV side |
5.5% |
1.46% |
Loading on Genset |
3.4 MW |
4.1 MW |
Savings : |
||
KWh Units per Litre of Furnace Oil |
4.09 units per litre |
4.17 units per litre |
Savings |
--- |
Approx. Rs.1.50 Crores p.a |
|
||
Indirect Benefit |
|
Avoidance of Over Temperature |
SAMPLE PERFORMANCE WITH LOAD CENTRIC BARON-ASHF/200 SYSTEM
Parameters |
Estimated Saving |
Actual Saving |
Electrical Parameters : |
||
KWHr Reduction |
41916 units |
45619 units |
KVA Reduction |
174 units |
166 units |
Current Reduction with Filter |
222 Amps |
240 Amps |
Voltage Stabilising with Filter |
3 Volts |
10 Volts |
5th Current Harmonics Reduction with Filter (in Magnitude) |
115 Amps |
166 Amps |
Savings |
||
Total Savings in Rupees |
Rs.5,44,476/- per annum |
Rs.5,41,037/- p.a |
BENEFITS
Due to the implementation of the Passive Harmonic Filter Systems at the points of generation, and the said problem of Overtemperature Tripping was avoided and the loading on the Genset was improved thereby reducing the cost of per unit generation.