IMPACT OF HARMONICS ON NEUTRAL LOADING - ACTIVE HARMONIC FILTER SYSTEMS |
||||||||||||||||||||||||||||||||
|
|
CHEMICAL INDUSTRY
The Plant has Single Phase Loads connected in considerable number. The problem of high neutral loading was reported which was leading to subsequent operational problems in the Loads connected. Hence Power Quality Analysis Study was conducted at site to identify the root cause and provide suitable Solution.
The Total Harmonic Distortion – Current and Voltage is recorded highest of values 60.0 % and 1.7 % respectively at the UPS outgoing. From the recorded level, it is clear that the Harmonic Distortion at UPS is quit higher, which will enhance the distribution losses due to high current flow. The 3rd Order Harmonics recorded of 50.1% is high.
Due to considerable amount of single Phase Loads fed through UPS System, Higher level of third order Zero Sequence Harmonics has lead to heavy neutral loading.
The root cause being the Third Order Harmonics, the basic necessity was to implement a Harmonic Filter System
The following harmonic spectrum shows that the significant 3rd order Harmonics have reduced significantly on installation of the Filter System thereby reducing the loading on the Neutral.
NEUTRAL CURRENT WITH & WITHOUT FILTER SYSTEM
IMPACT OF HARMONICS ON DISTRIBUTION CABLE LOADING AND SUPPLY DISTORTION PREAMBLE
The facility has several sensitive Loads like Broad Casting Units, which are fed through Online UPS Systems, which was resulting in High level of harmonic loading on distribution cable and supply voltage distortion.
Basic necessity of the system is identified as Hence recommendation was done to install 150A Active Harmonic Filter System at the UPS Feeder Incomer.
The above tabulation clearly indicates that on installation of Active Filter System at the UPS Feeder, the Apparent Current has reduced from 433 A to 393 A, with kVA reduction from 292 kVA to 273 kVA. The Voltage and Current THD have reduced significantly from 8.64 % to 4.57% by the suppression of wide range of Harmonics by the Active Filter
The following Trend Graphs clearly indicates the reduction of Harmonic Distortion levels at the UPS incomer with the implementation of the Active Filter System at the Point of Generation.
3 PHASE AVG. THD VOLTAGE ( %)
3 PHASE AVG. THD VOLTAGE ( %)
|
|||||||||||||||||||||||||||||||