PF CORRECTION FOR HIGLY FLUCTUATING LOAD PROFILE - DPFC SYSTEM

 

 

PF CORRECTION FOR HIGLY FLUCTUATING LOAD PROFILE – DPFC SYSTEM

 

PREAMBLE

 

Client had expressed their interest in improving the PF at Feeder and thereby avail the benefits of reduced apparent current stressing the cables and reduction of kVA. Hence Load Flow Study was conducted to identify the Load Profile and recommend a suitable system.


SITE ANALYSIS

   Parameters

   Readings logged

KVA

120

KW

100

KVAR

66

P.F

0.83

Current (amperes)

170


OBSERVATIONS AND INFERENCE

The analysis of the readings recorded during the time of measurement shows that the instantaneous PF of 0.83 is less.

The trend of the Reactive Power shows a highly fluctuating load profile.

The Level of Voltage and Current THD are within the limits of IEEE Standards for Harmonics.


SYSTEM DESIGN AND RECOMMENDATION

For the Fluctuating Load Profile recorded, the system needs to be implemented as a Dynamic PF Correction System, a centralized PF Correction System at the MV Panel.

In order to improve the PF from the existing level to 0.97, the DPFC Systems is designed to provide an output of 120 kVAr, with minimum step and configuration suiting the Transformer Compensation and base load compensation requirements.


PERFORMANCE

Parameters

Savings

KVA Reduction

20 KVA

Current Reduction with DPFC

30 Amps

PF

0.97

THD Voltage Harmonics

2.00%

THD Current Harmonics

7.50%

Improvement in Voltage Profile

2 Volts

 

POWER PARAMETERS

 

With DPFC, the reactive power Qti+ (KVAR) is kept at the optimum level, thereby maintaining an optimum KVA loading.

 

POWER PARAMETERS


With DPFC, the reactive power Qti+ (KVAR) is kept at the optimum level, thereby maintaining an optimum KVA loading.

POWER FACTOR


Without DPFC System the power factor is low, leading to higher nett current. 

With DPFC System, the power factor is stabilized at 0.97, thereby having reduction in Nett Current.  Without DPFC System, the power factor is at 0.82.

 

PHASE CURRENT


The Level of Nett Current is brought down by 30 amps with DPFC, throughout the recording period. The Load Currents are stabilized with DPFC, thereby improving the Voltage Regulation. 

 

BENEFIT

On implementing the DPFC System, the Apparent Current has reduced by 30 A and the kVA has reduced by 20 kVA.